| Alarm Code | Meaning | Likely Cause & Solution | | :--- | :--- | :--- | | | Internal EEPROM error | Faulty controller; replace unit. | | E1 | Probe 1 faulty (open circuit) | Broken probe, loose wire at terminals 2/3, or wrong S1P setting. | | E2 | Probe 1 short circuit | Moisture in probe tip, damaged probe, or short across terminals 2-3. | | HA | High temperature alarm | Temperature above ALU (alarm upper limit). Check compressor, refrigerant, fans. | | LA | Low temperature alarm | Temperature below ALL (alarm lower limit). Check setpoint, probe placement. | | PFA | Probe failure alarm – output forced | Controller is running a timed cycle because E1/E2 is active. Check probe wiring. |

A: The most common default is 3 (three). If that fails, try 5 , 55 , 22 , or 0 . If none work, the password has been changed by a previous technician. You may need to contact technical support for a backdoor reset code. eliwell sb655 c manual

| Terminal | Label | Function | Typical Connection | | :--- | :--- | :--- | :--- | | 1 | 12V | +12 Vdc output for probe (power supply) | Connect to probe + | | 2 | GND | Ground reference for probe | Connect to probe - | | 3 | PTC/NTC | Analog input for temperature probe (Probe 1) | Signal wire (typically white or yellow) | | 4 | N | Neutral (Power supply input) | 230V Neutral Line | | 5 | L | Live (Power supply input) | 230V Live Line | | 6 | NO | Normally Open output relay contact | Compressor contactor coil (L1) | | 7 | COM | Common output relay contact | Compressor contactor common | | 8 | NC | Normally Closed (rarely used) | Alarm circuit or unused | | Alarm Code | Meaning | Likely Cause

A: That is not an error. The display is showing that the compressor is in a minimum off-time delay (parameter dLy). It is protecting the compressor from short cycling. The countdown value will appear (e.g., “3” for 3 minutes remaining). | | HA | High temperature alarm |

If you are searching for the Eliwell SB655 C manual , you likely have a refrigeration or HVAC control panel in front of you that needs programming, troubleshooting, or an electrical connection check. The Eliwell SB655 C is a classic, highly reliable digital temperature controller widely used in commercial refrigeration, cold rooms, industrial freezers, and HVAC systems. However, without the manual, navigating its parameters and terminal blocks can be daunting.

This article serves as a complete digital handbook. We will cover everything from the technical specifications and terminal functions to step-by-step programming, parameter lists, alarm codes, and common wiring diagrams. The Eliwell SB655 C is a microprocessor-based digital temperature controller with an onboard relay output. It is part of Eliwell’s “Easy” series, known for its simplicity and robustness. The device is typically panel-mounted and features a bright 3-digit LED display, four buttons for navigation, and a user-friendly interface.

| Code | Parameter Name | Description | Typical Range | Recommended Setting | | :--- | :--- | :--- | :--- | :--- | | | Setpoint | Desired controlled temperature | LS to US | 2.0°C (cooler) / -18.0°C (freezer) | | Hy | Hysteresis | Differential (cut-in – cut-out). Compressor starts at SP+Hy, stops at SP. | 0.1 to 25.0°C | 2.0°C (reduces cycling) | | LS | Minimum Setpoint | Lower limit to lock SP | -50 to US | -30°C (freezer) / 0°C (cooler) | | US | Maximum Setpoint | Upper limit to lock SP | LS to 150°C | 8.0°C (cooler) / 0°C (freezer) | | OdO | On Delay Output | Delay before energizing output after power-up | 0 to 250 min | 2 min (protects compressor) | | dLy | Delay | Minimum off time for compressor | 0 to 60 min | 5 min (crucial for compressor life) | | PA | Password | Access code for parameter menu | 0 to 199 | 3 (default) | | C_F | Temperature Scale | Celsius or Fahrenheit | C / F | C (or F for USA) | | S1P | Probe 1 Type | Type of temperature probe | PtC / ntC | ntC (usually for NTC 10k) or PtC |